877
1 INTRODUCTION
This paper is an extension of work originally
presented in conference name [1].
The development of new methods and technical
schemes for measuring three-phase voltage
parameters for controlling autonomous generator sets
is justified by a fundamentally new approach to
controlling their voltage. The need to increase the
speed of the three-phase voltage sensor is caused by
the prospect of using asynchronous generators with
capacitor excitation on ships [2,3]. There was a need
for a voltage sensor that measures the average value
of the three-phase voltage of an autonomous
generator, the speed of which is unstable, for half the
alternating current period.
Improvement of autonomous power plants,
including marine transport facilities, improvement of
their technical and economic indicators is the main
trend in the development of ship's technology. For
example, the capacity of electrical equipment installed
on modern ships reaches 40% of the capacity of a
power plant, therefore, the choice of an optimal
composition of a power plant with improved
operational qualities contributes to an increase in the
efficiency of the power plant.
Currently, on sea-going ships, synchronous
generators are mainly used as sources of electricity,
which is explained by the simplicity of the technical
means for regulating their voltage. The multi-turn
excitation winding on the generator rotor makes it
possible to control the voltage of the synchronous
generator using relatively small currents.
However, this "simplicity" caused two other
problems: the rotating slip rings on the rotor and the
high inductance of the excitation circuit, which
significantly reduced the speed of the voltage
stabilization system.
As a result of numerous scientific and
technological developments of synchronous
generators and their excitation systems, generating
sets have been created that have practically exhausted
the possibilities for further improving the quality of
electricity [4].
Modern brushless synchronous generators with
inverted exciter and rotating diodes have eliminated
rotating contacts but have significantly complicated
the design of the generator. To increase the speed of
Measuring the Voltage of a Three-Phase Circuit in a
Generator Set Control System
L. Vyshnevskyi, M. Mukha, O. Vyshnevskyi & D. Vyshnevskyi
National University "Odessa Maritime Academy", Odessa, Ukraine
ABSTRACT: The article proposes a technical implementation of a high-speed voltage sensor in a three-phase
circuit of a generator set, the frequency of which changes in transient processes. Sequential differentiation,
rectification and intensification of phase voltages allows one to substantially reduce the influence of the current
frequency on the measured voltage during one current period.
http://www.transnav.eu
the International Journal
on Marine Navigation
and Safety of Sea Transportation
Volume 15
Number 4
December 2021
DOI: 10.12716/1001.15.04.21
878
voltage stabilization of synchronous generators,
multiple excitation current forcing systems are used.
Excitation of the asynchronous generator through
the stator circuit allows realizing a voltage regulation
system that is practically invariant from the load, [5-
8].
2 FEATURES OF AUTONOMOUS POWER SUPPLY
SYSTEMS
According to the authors, a radical way to modernize
an electric power plant is the use of asynchronous
generators with a squirrel-cage rotor and capacitor
excitation along the stator circuit, [3].
The voltage control of the asynchronous generator
is carried out on the stator circuit, i.e. along the load
circuit, therefore the inertia of the control and
disturbance channels are the same. As shown by the
research of the authors [2,5,8], this allows to create an
almost load-invariant voltage stabilization system.
The voltage control of the asynchronous generator
is carried out by switching to the three-phase stator
winding of the capacitor banks using triacs at certain
times when the voltages on the capacitor and the
phase winding of the generator are equal. In this case,
capacitors of different phases are switched at different
times, in accordance with the shifts of the phase
voltages. Therefore, the whole process of connecting a
three-phase unit takes time slightly less than the
network period.
2.1 Main part
The features of switching capacitor units determine
the requirements for the speed of the voltage sensor of
a three-phase network. The maximum speed of the
voltage stabilization system requires reliable
measurements of the RMS voltage for the three-
phase current period :
( )
2
0
1
T
s
U u t dt
T
=
In most of the known sinusoidal voltage sensors,
the average voltage value is measured instead of
the RMS value, which significantly reduces the
computational complexity of their implementation.
With insignificant nonlinear distortions, the RMS
voltage value is proportional to its amplitude ,
therefore such a replacement is quite justified.
The calculation of the voltage average value is
associated with the integration of the voltage
instantaneous value during the positive half-
cycle of the alternating current , [6,9]. In this
case, the fixation of the voltage measurement period is
carried out when the phase voltage passes through
zero.
A significant disadvantage of such sensors is the
dependence of the output signal not only on the
voltage , but also on the frequency of the current
, as shown in our article [1]:
In marine generator sets with a diesel drive engine,
a significant frequency deviation is allowed, both in
steady-state and in transient modes, [10-12]. In this
case, the instability of the frequency of the current
will introduce significant errors in the output signal of
the voltage sensor, [4].
The article [13] describes and investigates a
method for calculating the average value of an
alternating voltage by sequential differentiation,
rectification, and integration of phase voltages
during a half-period of alternating current :
( )
/2
0
2
T
di m
du t
u dt U
dt
==
The integration period is set by a
synchronizing pulse which action in during positive
value of the measured voltage. At the end of the
measurement process, the amplitude of the sync pulse
becomes equil zero, the value of the integral is
memorized and stored until the next measurement
period.
Simple circuit solutions of analog voltage sensors
are proposed for both single-phase and three-phase
circuits, which made it possible to significantly reduce
the dependence of the output signal of the voltage
sensor on the current frequency , [5,6], Fig. 1. In
the frequency range from 40 to 50 Hz, the voltage
measurement error is about 2%, at it is -
0.6%, and at it is +0.9%.
Figure 1. Dependence of the output signal of the AC voltage
sensor on the current frequency: integration of the
rectified voltage; preliminary differentiation,
rectification, and integration of voltage
A diagram of the analog implementation of the
proposed method for a three-phase network is shown
in Fig. 2.
879
Figure 2. Analog part of the sensor for the average voltage
of a three-phase network
Galvanic isolation and lowering of phase voltages
are provided by three transformers TR1, TR2 and TR3
with two output windings having a common point,
which makes it possible to realize full-wave
rectification of the alternating voltage of each phase
using diodes . Differentiation of input
signals is performed by RC - circuits .
Further addition and integration of the measured
signals is carried out by the operational amplifier
, the integration constant of which is determined
by the product of the capacitance on the
resistance (R14, R15). Synchronization with the
mains and discharge of the integrating capacitor is
performed by pulse shunting with the field-effect
transistor , which is controlled by the operational
amplifier . Synchronizing circuit is
connected to the secondary winding of the phase
transformer. Oscillograms of the rectified phase
voltages and the sensor output signal are shown in
Fig. 3.
Figure 3. Oscillograms of the voltage sensor of a three-phase
network
The main advantage of the proposed circuit is the
close to linear waveform at the output of the
operational amplifier at symmetrical phase
voltages. In this case, the slope of the characteristic is
proportional to the amplitude of the phase voltages.
This makes it possible to quickly measure the
amplitude of symmetrical voltages.
However, with unbalanced voltages, the form of
the charge of the capacitor ceases to be strictly
linear, but at the end of the half-period , the
value of the output signal is proportional to the
average value of the unbalanced phase voltages.
When regulating the voltage of an autonomous
generator, the deviation of the average value of the
phase voltages from the given one is used, depending
on which a control action is formed on the excitation
system of the generator.
Therefore, the authors checked the error of
measuring the average value of the asymmetric phase
voltages. The voltage amplitude of one of the phases
varied from 0 to 150% of the nominal value at
100% amplitudes of the other two phases. The
obtained values of the output voltage of the
sensor in relative units were compared with the
theoretical ones shown by the dotted line. These
results are shown in Fig. 4.
Figure 4. Accuracy and error in measuring the average
value of asymmetric phase voltages
When one of the voltages changes from 80 to 120%,
the average value of the three voltage phases changes
from 0.933 to 1.067. In this case, the sensor error is
within the range of 0.1 - 0.6%.
Computer and physical modeling of the proposed
three-phase voltage sensor has shown that with an
asymmetry of the generator phase voltage up to 50%,
the output voltage of the sensor retains a sawtooth
shape, close to linear.
With a complete disconnection of one of the
phases, the error was 3.2%. Oscillograms are shown in
Fig. 5.
Figure 5. Oscillograms of the voltage sensor of a three-phase
network when one of the phases is disconnected
880
The voltage waveform in Fig. 5 is already
significantly different from the linear one. The voltage
sensor circuit of a three-phase network remains
operational even when two phases are disconnected,
i.e. for single-phase use. Oscillograms are shown in
Fig. 6.
Figure 6. Oscillograms of the voltage sensor of a three-phase
network when two phases are disconnected (single-phase
mode)
The process of integrating the measured signal is
quite simply implemented in software in the digital
part of the sensor by summation after differentiation
and rectification of signals from phase voltages.
Synchronization of the sensor with the power grid
is also easily implemented by the controller by
comparing the instantaneous signal of one of the
phases with a given constant level.
At the same time, the operations of differentiation
and rectification are implemented by local
radioelements using capacitors, resistors and diodes,
i.e. without ICs containing operational amplifiers.
This circumstance makes it possible to optimize the
ratio of the analog and digital parts of the sensor
according to the criterion of ease of implementation.
Such a diagram of a three-phase voltage sensor is
shown in Fig. 7. Electrical isolation, differentiation
and rectification of phase voltages are performed by
the analog part of the circuit, and integration and
synchronization are performed by the controller,
Fig.8.
Figure 7. Circuit of a three-phase voltage sensor with digital
integration and formation of a synchronization pulse
Transformers TR1-TR3 reduce phase voltages and
provide electrical isolation of power and measuring
circuits. Capacitors C1-C6 and resistors R1, R2, R4, R5,
R7, R8 perform differentiation, and diodes D1-D6
rectify phase voltages. Then the analog signals are fed
to the analog ports A1-A3 of the controller. The
controller interface (terminals 1 to 8) outputs some
bytes of information from the voltage sensor in digital
form, and digital-to-analog conversion of the output
signal of the three-phase circuit voltage sensor is
performed on the resistors R15-R22 and R6.
A resistor-diode divider R10-D7-R11 is used for
synchronizing with the mains voltage, the output
signal of which is put to port A0.
Figure 8. The operation oscillograms of a three-phase
voltage sensor with digital integration and synchronization
with the network
In Fig. 9 shows the operation of the voltage sensor
(green) and the regulator with integral control law
(red).
The controller has a digital integral regulator - pins
9-12. The digital-to-analog conversion of the regulator
signal is performed on resistors R9, R12-R14 and R23.
The setpoint of the regulator input to the controller by
means of the resistors R3 and RV1 via port A4.
Figure 9. An output signals oscillograms of the integral
controller:
a - an increase in the control action with a minimum
intensity
b - decrease in control action with threefold intensity
When simulating and for setting up the program
code, pins 1-8 can be used to output internal program
variables. For example, in Fig. 9 shows the operation
of the voltage sensor and regulator with an integral
881
control law. In Fig. 9, a, b, the upper diagram reflects
the output signal of the integral regulator, and the
lower diagram illustrates the result of software
integration of the sensor signal of a three-phase
circuit.
Digital integration of the sensor signal of a three-
phase circuit and the formation of a synchronizing
pulse allows you to optimize the ratio of the analog
and digital parts of the sensor according to the ease of
implementation criterion.
3 CONCLUSIONS
The developed sensor of the average value of three-
phase voltage measures in half the period of the
alternating voltage.
Preliminary differentiation of phase voltages made
it possible to reduce the dependence of the sensor
output signal on the current frequency by 9 ... 12
times.
The linearity of the sawtooth output of a three-
phase transducer can significantly improve the
performance of the transducer.
The proposed method and scheme for the
implementation of a three-phase sensor remains
operational in case of phase failure and for single-
phase use.
REFERENCES
1. Vishnevsky, L., Mukha, M., Vishnevsky, O., Vishnevsky,
D.: Voltage Sensor of the Autonomous Generating Set.
In: 2020 IEEE 15th International Conference on
Advanced Trends in Radioelectronics,
Telecommunications and Computer Engineering
(TCSET). pp. 712715 (2020).
https://doi.org/10.1109/TCSET49122.2020.235525.
2. Vishnevsky, L.V.: Optimal voltage control of an
asynchronous generator. In: Vishnevsky, L.V. and
Novosad, I. (eds.) Automation of ship technical facilities:
scientific and technical collection of works. pp. 1928
Odessa: OHMA (1993).
3. Vishnevsky, L.V., Mukha, M.Y., Drankova, A.O.:
Improving the Energy Efficiency of Ship Electric
Installations by Using Asynchronous Generators. The
Proceedings of the Institute of Electrodynamics of the
National Academy of Sciences of Ukraine. 56, 4056
(2020). https://doi.org/10.15407/publishing2020.56.040.
4. ISO 8528-3:2005: Reciprocating internal combustion
engine driven alternating current generating sets Part
3: Alternating current generators for generating sets.
(2005).
5. Vishnevsky, L.V., Mukha, M.Y., Kuan, D.M.: Voltage
control of stand-alone asynchronous generating sets.
LAP LAMBERT Academic Publishing (2016).
6. Vishnevsky, D.: Optimization of the voltage regulation
law of an asynchronous generator. Energy saving,
energy, energy audit. 12, 131, 4046 (2014).
7. Vishnevsky, L.: Time Constants of an Asynchronous
Generator with Capacitor Excitation. In: Vishnevsky, L.
and Mukha, M. (eds.) Electrical engineering and
electrical equipment. pp. 2126 (1999).
8. Vishnevsky, L.: Transient quality in pulsed voltage
stabilization systems for marine diesel generators. In:
Vishnevsky, L., Mukha, M., and Veretennik, A. (eds.)
Automation of ship technical facilities. pp. 1318 ,
Odessa: OSMA (2002).
9. Mustafa, G.: Modular multilevel converters for
balancing and filtering mains voltage in the vicinity of
AC traction substation. In: Mustafa, G., Gusev, S.,
Ershov, A., and Luganskay, I. (eds.) Vesnik NTU. pp.
495500 (2015).
10. Electrical Installations in Ships: Part 101: Definitions and
General Requirements, IEC Standard 60092-101. (2018).
11. ISO 3046-4:2009: Reciprocating internal combustion
engines Performance Part 4: Speed governing. (2018).
12. ISO 8528-1:2018: Reciprocating internal combustion
engine driven alternating current generating sets Part
1: Application, ratings and performance. (2018).
13. Bulatov, R.: Improving the voltage asymmetry sensors of
three-phase electric machine generator sets. Bulletin of
UlSTU. 4, 4041 (2011).